 A buzzer sounds
 The buzzer keeps sounding.

When the GP's buzzer keeps sounding, approximate 2 factors can be thought for it.

GP images

Factor 1 : FThe buzzer output bit in the system data area of the GP is ON.
There is the bit to sound the buzzer of the GP in the GP's system data area (When connecting the PLC, Bit 01 of +14, In case of Memory Link, Bit 01 of Address 11)
 
  If you use the bit for a switch or turn it on with the ladder on the PLC side, the buzzer of the GP will start sounding.

Recovery Method
Pull out the communication cable with PLC and turn ON/OFF the power supply of the GP. Then the values in the system data area will be reset and the buzzer output will be OFF.
When the communication cable with PLC cannot be pulled out, turn OFF from the PLC side the buzzer output bit in the system data area (Bit 01 of +14 when connecting the PLC, in case of Memory Link, Bit 01 of Address 11).

Factor 2 : FGP's system is damaged.
When the GP's system is damaged by some factors, the GP's touch doesn't function and the buzzer won't stop. In most of the cases, the error, [System Error] is displayed soon after. (There's a case that no error is displayed.)

Recovery Method
Pull out the communication cable with the PLC and turn ON/OFF the power supply of the GP. When the symptom still remains, send the project file to GP again with Forced Setup.
 