Errors displayed with the LT3000 series
Error Message |
Cause and Troubleshooting |
Browse |
ID on I/O board does not match. | The I/O board cannot be normally recognized. The I/O board may have a fault. Turn ON the power switch again, and execute forced-transfer of the project file. If this same error persists, the I/O board may have a fault. Please contact the Pro-face customer care center. |
|
Failed to transfer firmware to I/O board. Use forced transfer method. | The I/O board firmware file is damaged. The I/O board firmware cannot be normally transferred to the I/O board flash memory. Execute forced-transfer of a project file. If this same error persists, the I/O board may have a fault. Please contact the Pro-face customer care center. |
This error appears when using the standard driver, STD driver (STD4S driver), or an EXM driver.
When an error occurs, the error code is stored in the system variable (#L_ExIOStatus).
Any of the following error messages appears depending on the result of the I/O monitoring of the module connected to the STD driver.
Error Code |
Error Message |
Cause and Solution |
RGEE001 | Invalid module type | The specified module type is not supported. The project file may not have been sent correctly. Transfer the project file again. |
RGEE002 | Setting value error | The type of the variable assigned to the terminal is invalid, or the terminal setting is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEE003 | Device out-of-range error | The variable address assigned to the terminal is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEE004 | Too many term. setting | The number of terminals is invalid. (The number of terminals is excessive.) The project file may not have been sent correctly. Transfer the project file again. |
RGEE005 | Terminal setting order error | The terminal numbers are not arranged in ascending order. The project file may not have been sent correctly. Transfer the project file again. |
RGEE006 | Insufficient number of terminal registration | The number of terminals is invalid (insufficient number of terminals). The project file may not have been sent correctly. Transfer the project file again. |
RGEE007 | Module settings duplicated | Module registration is duplicated. The project file may not have been sent correctly. Transfer the project file again. |
RGEE008 | Excess module settings | The number of modules is invalid (excess number of terminals). The project file may not have been sent correctly. Transfer the project file again. |
RGEE009 | Driver settings duplicated | Driver registration is duplicated. The project file may not have been sent correctly. Transfer the project file again. |
RGEE010 | Inconsistent I/O settings | The terminal setting is invalid (inconsistent I/O setting of the module). The project file may not have been sent correctly. Transfer the project file again. |
RGEE011 | Inconsistent bit/integer type | The terminal setting is invalid (inconsistent variable type setting of the module). The project file may not have been sent correctly. Transfer the project file again. |
RGEE012 | Setting level value error | The driver is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEE013 | Data obtaining address error | The driver information or controller information is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEE014 | Invalid driver ID | Because an error occurred during driver/module registration, the driver/module has not been registered. The project file may not have been sent correctly. Transfer the project file again. |
RGEE015 | Module setting order error | The module numbers are not arranged in ascending order. The project file may not have been sent correctly. Transfer the project file again. |
RGEE016 | File version mismatch | The driver file version does not match. The project file may not have been sent correctly. Transfer the project file again. |
RGEE050 | I/O board ID mismatch | Wrong I/O board is inserted. The display type might not be correct. Check the Display Unit type and transfer the project file again. |
RGEE051 | Unsupported model | The model does not support this driver. The display type might not be correct. Check the Display Unit type and transfer the project file again. |
RGEE052 | I/O init. error | The system failed during I/O board initialization. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE053 | I/O ROM error | An error occurred with the I/O board system ROM. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE054 | I/O RAM error | An error occurred with the I/O board system RAM. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE055 | I/O microprocessor err | An error occurred with the I/O board microprocessor. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE056 | I/O IF RAM error | An error occurred with the I/O board system I/F RAM. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE057 | I/O E2PROM error | An error occurred with the I/O board system E2PROM. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE100 | I/O board error | The I/O board is not responding. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE101 | Special I/O error | An error occurred with the special I/O parameter setting. The parameter setting is invalid. Correct the parameter setting, and issue a parameter change request. |
RGEE102 | Acc/Dec table error | An error occurred with the special I/O parameter setting. The parameter setting is invalid. Correct the parameter setting, and issue a speed-up/down table preparation request. |
RGEE103 | Init. parameter error | An error occurred with the special I/O parameter setting for initial processing. The parameter setting is invalid. Correct the parameter setting, and issue a parameter change request. |
RGEE108 | Analog data range error | Upper limit and lower limit setting values of the analogue module are faulty. The project file may not have been sent correctly. Transfer the project file again. |
RGEE127 | Analog output error | Analogue output request flag write is not completed. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE128 | Output data error | The output data is out of the setting range, or the data output is stopped. Output data within the setting range. This error code continues appearing until the controller is reset. |
RGEE129 | Analog power error | An external power supply is not connected to the analog module. Connect a power supply to the analog module. This error code continues to appear until the controller is reset. |
RGEE130 | Input data error | The input data is out of the setting range, or the data input is stopped. Input data within the setting range. This error code continues to appear until the controller is reset. |
RGEE131 | Pulse output error | There is a problem with the pulse output. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEE132 | Analog input wire error | The wiring in the analog input cable may be damaged. Connect an undamaged analog input cable. |
RGEE133 | Temperature wire error | The wiring in the temperature input cable may be damaged. Connect an undamaged temperature input cable. |
RGEE134 | Temperature range error | The settings for the temperature input's measurement object are incorrect, or the measurement object failed. Connect a measurement object that is working correctly. |
RGEE200 | Word read error | The system failed while reading integer-type terminal data. The project file may not have been sent correctly. Transfer the project file again. |
RGEE201 | Bit read error | The system failed while reading bit-type terminal data. The project file may not have been sent correctly. Transfer the project file again. |
RGEE202 | Word write error | The system failed while writing integer-type terminal data. The project file may not have been sent correctly. Transfer the project file again. |
RGEE203 | Bit write error | The system failed while writing bit-type terminal data. The project file may not have been sent correctly. Transfer the project file again. |
For LT4000 Series, you can save the error information in the system variable (#L_ExIOStatus) and at the same time have it reflected in a user-defined I/O variable (to store analog values or temperatures).
By reflecting error information in user-defined variables, you can check multiple errors at one time. (When an error code is stored in #L_ExIOStatus, you can check 1 error only.)
Error codes and messages stored in #L_IOStatus |
Values reflected in user-defined I/O variable |
|
RGEE130 | Input data error | Dec: 65535 / HEX: FFFF |
RGEE132 | Analog input wire error | Dec: 65534 / HEX: FFFE |
RGEE133 | Temperature wire error | Dec: 65534 / HEX: FFFE |
RGEE134 | Temperature range error | Dec: 65535 / HEX: FFFF |
Any of the following error messages appears depending on the result of the I/O monitoring of the module connected to the EXM driver.
Error Code |
Error Message |
Cause and Solution |
RGEF001 | Invalid model | The specified module type is not supported. The project file may not have been sent correctly. Transfer the project file again. |
RGEF002 | Setting value error | The type of the variable assigned to the terminal is invalid, or the terminal setting is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEF003 | Device out-of-range error | The variable address assigned to the terminal is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEF004 | Too many terminals setting | The number of terminals is invalid. (The number of terminals is excessive.) The project file may not have been sent correctly. Transfer the project file again. |
RGEF005 | Terminal setting order error | The terminal numbers are not arranged in ascending order. The project file may not have been sent correctly. Transfer the project file again. |
RGEF006 | Insufficient number of terminal registration | The number of terminals is invalid (insufficient number of terminals). The project file may not have been sent correctly. Transfer the project file again. |
RGEF007 | Module settings duplicated | Module registration is duplicated. The project file may not have been sent correctly. Transfer the project file again. |
RGEF008 | Excess module settings | The number of modules is invalid (excess number of terminals). The project file may not have been sent correctly. Transfer the project file again. |
RGEF009 | Driver settings duplicated | Driver registration is duplicated. The project file may not have been sent correctly. Transfer the project file again. |
RGEF010 | Inconsistent I/O settings | The terminal setting is invalid (inconsistent I/O setting of the module). The project file may not have been sent correctly. Transfer the project file again. |
RGEF011 | Inconsistent bit/integer type | The terminal setting is invalid (inconsistent variable type setting of the module). The project file may not have been sent correctly. Transfer the project file again. |
RGEF012 | Setting level value error | The driver is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEF013 | Data obtaining address error | The driver information or controller information is invalid. The project file may not have been sent correctly. Transfer the project file again. |
RGEF014 | Invalid driver ID | Because an error occurred during driver/module registration, the driver/module has not been registered. The project file may not have been sent correctly. Transfer the project file again. |
RGEF015 | Module setting order error | The module numbers are not arranged in ascending order. The project file may not have been sent correctly. Transfer the project file again. |
RGEF016 | File version mismatch | The driver file version does not match. The project file may not have been sent correctly. Transfer the project file again. |
RGEF050 | I/O board ID mismatch | Wrong I/O board is inserted. The display type might not be correct. Check the Display Unit type and transfer the project file again. |
RGEF051 | Unsupported model | The model does not support this driver. The display type might not be correct. Check the Display Unit type and transfer the project file again. |
RGEF052 | I/O board init. error | The system failed during I/O board initialization. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEF100 | Module init. error | The module may not be properly connected. Reconnect the module properly and turn the power on again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEF101 | Module init. resp err | |
RGEF102 | Module init. send err | |
RGEF103 | Module init. rcv. err | |
RGEF104 | Module init. end err | |
RGEF105 | Module connections err | The connected I/O board does not match. The display model may be different. Check the display model, and transfer the project file again. |
RGEF106 | Unsupported module | The connected module is not supported. Remove the unsupported module and then turn ON electric power again. |
RGEF107 | Mode setting error | Mode setting value is faulty. The project file may not have been sent correctly. Transfer the project file again. |
RGEF108 | Analog data range error | There a problem with the analog module's upper and lower limit values. The project file may not have been sent correctly. Transfer the project file again. |
RGEF109 | Module settings error | The module does not operate due to the data mismatch between the connected module and the set data. The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again. |
RGEF120 | Module validation err | There is a mismatch between a connected module and the set data, however the module is partially running. The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again. |
RGEF121 | Module response error | The module may not be properly connected. Reconnect the module properly and turn the power on again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEF122 | Module send error | |
RGEF123 | Module receive error | |
RGEF124 | Module comm. setting | Difficulties in transmission data. The module may not be properly connected. Reconnect the module properly and turn the power on again. The display unit may be faulty. Please contact the Pro-face customer care center. |
RGEF125 | Module ACK error | The module may not be properly connected. Reconnect the module properly and turn the power on again. The display unit may be faulty. Please contact the Pro-face customer care center. |
RGEF126 | Module comm. error | |
RGEF127 | Analog output error | Analog output request flag did not complete writing. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center. |
RGEF128 | Output data error | Output data is outside the settings range, or has stopped. Output data that is within the settings range. This error code continues to appear until the controller is reset. |
RGEF129 | Analog power error | An external power supply is not connected to the analog module. Connect a power supply to the analog module. This error code continues to appear until the controller is reset. |
RGEF130 | Input data error | Input data is outside the settings range, or has stopped. Input data that is within the settings range. Or the analogue input cable might be damaged. Connect an undamaged analogue input cable. This error code continues to appear until the controller is reset. |
RGEF200 | Word read error | The system failed while reading integer-type terminal data. The project file may not have been sent correctly. Transfer the project file again. |
RGEF201 | Bit read error | The system failed while reading bit-type terminal data. The project file may not have been sent correctly. Transfer the project file again. |
RGEF202 | Word write error | The system failed while writing integer-type terminal data. The project file may not have been sent correctly. Transfer the project file again. |