T.7.4 When the LT Series is used

Errors displayed with the LT3000 series

Error Message

Cause and Troubleshooting

Browse

ID on I/O board does not match.

The I/O board cannot be normally recognized. The I/O board may have a fault.

Turn ON the power switch again, and execute forced-transfer of the project file. If this same error persists, the I/O board may have a fault. Please contact the Pro-face customer care center.

M.12.3 Forcing the transfer of project files

Failed to transfer firmware to I/O board. Use forced transfer method.

The I/O board firmware file is damaged. The I/O board firmware cannot be normally transferred to the I/O board flash memory.

Execute forced-transfer of a project file. If this same error persists, the I/O board may have a fault. Please contact the Pro-face customer care center.

I/O driver errors

This error appears when using the standard driver, STD driver (STD4S driver), or an EXM driver.

When the STD driver is used

When the EXM driver is used

When the STD driver is used

Any of the following error messages appears depending on the result of the I/O monitoring of the module connected to the STD driver.

Error Code

Error Message

Cause and Solution

RGEE001

Invalid module type

The specified module type is not supported.

The project file may not have been sent correctly. Transfer the project file again.

RGEE002

Setting value error

The type of the variable assigned to the terminal is invalid, or the terminal setting is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEE003

Device out-of-range error

The variable address assigned to the terminal is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEE004

Too many term. setting

The number of terminals is invalid. (The number of terminals is excessive.)

The project file may not have been sent correctly. Transfer the project file again.

RGEE005

Terminal setting order error

The terminal numbers are not arranged in ascending order.

The project file may not have been sent correctly. Transfer the project file again.

RGEE006

Insufficient number of terminal registration

The number of terminals is invalid (insufficient number of terminals).

The project file may not have been sent correctly. Transfer the project file again.

RGEE007

Module settings duplicated

Module registration is duplicated.

The project file may not have been sent correctly. Transfer the project file again.

RGEE008

Excess module settings

The number of modules is invalid (excess number of terminals).

The project file may not have been sent correctly. Transfer the project file again.

RGEE009

Driver settings duplicated

Driver registration is duplicated.

The project file may not have been sent correctly. Transfer the project file again.

RGEE010

Inconsistent I/O settings

The terminal setting is invalid (inconsistent I/O setting of the module).

The project file may not have been sent correctly. Transfer the project file again.

RGEE011

Inconsistent bit/integer type

The terminal setting is invalid (inconsistent variable type setting of the module).

The project file may not have been sent correctly. Transfer the project file again.

RGEE012

Setting level value error

The driver is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEE013

Data obtaining address error

The driver information or controller information is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEE014

Invalid driver ID

Because an error occurred during driver/module registration, the driver/module has not been registered.

The project file may not have been sent correctly. Transfer the project file again.

RGEE015

Module setting order error

The module numbers are not arranged in ascending order.

The project file may not have been sent correctly. Transfer the project file again.

RGEE016

File version mismatch

The driver file version does not match. The project file may not have been sent correctly. Transfer the project file again.

RGEE050

I/O board ID mismatch

Wrong I/O board is inserted.

The display type might not be correct. Check the Display Unit type and transfer the project file again.

RGEE051

Unsupported model

The model does not support this driver.

The display type might not be correct. Check the Display Unit type and transfer the project file again.

RGEE052

I/O init. error

The system failed during I/O board initialization.

The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE053

I/O ROM error

An error occurred with the I/O board system ROM.

The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE054

I/O RAM error

An error occurred with the I/O board system RAM.

The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE055

I/O microprocessor err

An error occurred with the I/O board microprocessor.

The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE056

I/O IF RAM error

An error occurred with the I/O board system I/F RAM.

The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE057

I/O E2PROM error

An error occurred with the I/O board system E2PROM.

The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE100

I/O board error

The I/O board is not responding. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE101

Special I/O error

An error occurred with the special I/O parameter setting.

The parameter setting is invalid. Correct the parameter setting, and issue a parameter change request.

RGEE102

Acc/Dec table error

An error occurred with the special I/O parameter setting.

The parameter setting is invalid. Correct the parameter setting, and issue a speed-up/down table preparation request.

RGEE103

Init. parameter error

An error occurred with the special I/O parameter setting for initial processing.

The parameter setting is invalid. Correct the parameter setting, and issue a parameter change request.

RGEE108

Analog data range error

Upper limit and lower limit setting values of the analogue module are faulty. The project file may not have been sent correctly. Transfer the project file again.

RGEE127

Analog output error

Analogue output request flag write is not completed. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE128

Output data error

The output data is out of the setting range, or the data output is stopped. Output data within the setting range. This error code continues appearing until the controller is reset.

RGEE129

Analog power error

An external power supply is not connected to the analog module. Connect a power supply to the analog module. This error code continues to appear until the controller is reset.

RGEE130

Input data error

The input data is out of the setting range, or the data input is stopped. Input data within the setting range. This error code continues to appear until the controller is reset.

RGEE131

Pulse output error

There is a problem with the pulse output. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEE132

Analog input wire error

The wiring in the analog input cable may be damaged. Connect an undamaged analog input cable.

RGEE133

Temperature wire error

The wiring in the temperature input cable may be damaged. Connect an undamaged temperature input cable.

RGEE134

Temperature range error

The settings for the temperature input's measurement object are incorrect, or the measurement object failed. Connect a measurement object that is working correctly.

RGEE200

Word read error

The system failed while reading integer-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.

RGEE201

Bit read error

The system failed while reading bit-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.

RGEE202

Word write error

The system failed while writing integer-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.

RGEE203

Bit write error

The system failed while writing bit-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.

 

When the EXM driver is used

Any of the following error messages appears depending on the result of the I/O monitoring of the module connected to the EXM driver.

Error Code

Error Message

Cause and Solution

RGEF001

Invalid model

The specified module type is not supported.

The project file may not have been sent correctly. Transfer the project file again.

RGEF002

Setting value error

The type of the variable assigned to the terminal is invalid, or the terminal setting is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEF003

Device out-of-range error

The variable address assigned to the terminal is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEF004

Too many terminals setting

The number of terminals is invalid. (The number of terminals is excessive.) The project file may not have been sent correctly. Transfer the project file again.

RGEF005

Terminal setting order error

The terminal numbers are not arranged in ascending order.

The project file may not have been sent correctly. Transfer the project file again.

RGEF006

Insufficient number of terminal registration

The number of terminals is invalid (insufficient number of terminals).

The project file may not have been sent correctly. Transfer the project file again.

RGEF007

Module settings duplicated

Module registration is duplicated.

The project file may not have been sent correctly. Transfer the project file again.

RGEF008

Excess module settings

The number of modules is invalid (excess number of terminals).

The project file may not have been sent correctly. Transfer the project file again.

RGEF009

Driver settings duplicated

Driver registration is duplicated.

The project file may not have been sent correctly. Transfer the project file again.

RGEF010

Inconsistent I/O settings

The terminal setting is invalid (inconsistent I/O setting of the module).

The project file may not have been sent correctly. Transfer the project file again.

RGEF011

Inconsistent bit/integer type

The terminal setting is invalid (inconsistent variable type setting of the module).

The project file may not have been sent correctly. Transfer the project file again.

RGEF012

Setting level value error

The driver is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEF013

Data obtaining address error

The driver information or controller information is invalid.

The project file may not have been sent correctly. Transfer the project file again.

RGEF014

Invalid driver ID

Because an error occurred during driver/module registration, the driver/module has not been registered.

The project file may not have been sent correctly. Transfer the project file again.

RGEF015

Module setting order error

The module numbers are not arranged in ascending order.

The project file may not have been sent correctly. Transfer the project file again.

RGEF016

File version mismatch

The driver file version does not match.

The project file may not have been sent correctly. Transfer the project file again.

RGEF050

I/O board ID mismatch

Wrong I/O board is inserted. The display type might not be correct. Check the Display Unit type and transfer the project file again.

RGEF051

Unsupported model

The model does not support this driver. The display type might not be correct. Check the Display Unit type and transfer the project file again.

RGEF052

I/O board init. error

The system failed during I/O board initialization.

The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEF100

Module init. error

The module may not be properly connected. Reconnect the module properly and turn the power on again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEF101

Module init. resp err

RGEF102

Module init. send err

RGEF103

Module init. rcv. err

RGEF104

Module init. end err

RGEF105

Module connections err

The connected I/O board does not match. The display model may be different. Check the display model, and transfer the project file again.

RGEF106

Unsupported module

The connected module is not supported. Remove the unsupported module and then turn ON electric power again.

RGEF107

Mode setting error

Mode setting value is faulty. The project file may not have been sent correctly. Transfer the project file again.

RGEF108

Analog data range error

There a problem with the analog module's upper and lower limit values. The project file may not have been sent correctly. Transfer the project file again.

RGEF109

Module settings error

The module does not operate due to the data mismatch between the connected module and the set data. The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again.

RGEF120

Module validation err

There is a mismatch between a connected module and the set data, however the module is partially running. The setup information in the project and the connected module are different. Connect the specified module, and turn ON the power switch again.

RGEF121

Module response error

The module may not be properly connected. Reconnect the module properly and turn the power on again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEF122

Module send error

RGEF123

Module receive error

RGEF124

Module comm. setting

Difficulties in transmission data. The module may not be properly connected. Reconnect the module properly and turn the power on again. The display unit may be faulty. Please contact the Pro-face customer care center.

RGEF125

Module ACK error

The module may not be properly connected. Reconnect the module properly and turn the power on again. The display unit may be faulty. Please contact the Pro-face customer care center.

RGEF126

Module comm. error

RGEF127

Analog output error

Analog output request flag did not complete writing. The project file may not have been sent correctly. Transfer the project file again. If this error persists, the GP unit may be faulty. Please contact the Pro-face customer care center.

RGEF128

Output data error

Output data is outside the settings range, or has stopped. Output data that is within the settings range. This error code continues to appear until the controller is reset.

RGEF129

Analog power error

An external power supply is not connected to the analog module. Connect a power supply to the analog module. This error code continues to appear until the controller is reset.

RGEF130

Input data error

Input data is outside the settings range, or has stopped. Input data that is within the settings range. Or the analogue input cable might be damaged. Connect an undamaged analogue input cable. This error code continues to appear until the controller is reset.

RGEF200

Word read error

The system failed while reading integer-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.

RGEF201

Bit read error

The system failed while reading bit-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.

RGEF202

Word write error

The system failed while writing integer-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.

RGEF203

Bit write error

The system failed while writing bit-type terminal data.

The project file may not have been sent correctly. Transfer the project file again.