No scan time can be assured when a program is being uploaded.
No scan time can be assured when a CF/SD card is being read.
When an error arises in the logic or the I/O driver, the scan time is delayed by approximately 10ms.
When many devices are connected to the network, the scan time may be delayed.
It is recommended to physically separate the network into a control network, an information network, and others if necessary.
To be more specific, configure a PC with two network cards and configure the control network that includes the AGP on one card and configure the information network on the other. In other words, separate the network into two groups on the PC.
When movies are recorded/played using the multimedia function while the logic is in use, movie recording/playback may stop.
Please note that data updates between a device/PLC and the logic program are not synchronized when the device/PLC address (excluding internal addresses) is used in the logic program.
The data value is sometimes undefined when the logic program starts, and is not updated until communication with the device/PLC is established. Check that the device/PLC address data has been updated before using it in the logic program.
For example, a special relay (always on) is used for a device/PLC.
Device/PLC: Special relay (always on)
Logic program: Use the special relay in the logic program and check that the special relay is on before using the device/PLC address. If there are several devices/PLCs, a different relay is required for each device.
You cannot use write-only addresses for devices/PLCs in logic programs. For the list of write-only addresses, refer to the "GP-Pro EX Device Connection Manual".
If the same address (except for variables) is specified as a word address and as a bit address and used in multiple instructions, data between the word and bit specified addresses may be different in the same scan.
Example: The NO instruction [PLC1]D0000.00 will not show the data set in the MOV instruction [PLC1]D0000. Even if "1" is written in the variable "Data", the change is shown on [PLC1]D0000.00 only after a few scans.
To avoid this problem, do the following.
Specify bits after moving data from the address to a variable (rung 2)
When updating data on the device/PLC as a result of the logic program, make sure you use the MOV instruction (rung 5)
If the logic program includes operations for writing to the device/PLC address, the following phenomenon may occur, depending on the communication speed and the number of device/PLC addresses to write to:
When the display unit starts up, parts set up with the device/PLC address do not display.
Change screen operations take extra time.
Writing to the device/PLC fails.
This occurs due to excess write operations from the logic program to the device/PLC.
To avoid this problem, do the following: Increase the transmission speed with the device/PLC.
Adjust the number of addresses to write to the device/PLC.
Adjust the number of addresses used to write to the device/PLC. You can use operand (D) to specify device/PLC addresses.
The number of addresses that you can reference is as follows.
For example, when updating data in the logic every 10 ms, in the following system use a maximum value of 20.
Device/PLC: MELSEC FX
Communication speed: 115200 bps
Address updates: Medium speed
By using the system variable #L_RefreshEnable in the logic program, you can control write operations to the device/PLC so that they occur only after communication with the device/PLC has been checked.
30.16.1.1 GP-3300 Series Scan Time Delay
30.16.1.2 GP-3400/3500/3600/3750 Series Scan Time Delay
When you run the following operations on the SP5000 series, the scan time cannot be assured.
Online Editing
Communication, including transfer, with peripheral equipment connected to the USB port (Type A mini B)