When you use Simulation Feature, it’s necessary to transfer a program for Simulation to GP in advance. However if you try Simulation without a program transferred to GP, [no simulation information]'s displayed. |
Check the following items.
|
|
1. |
If the PLC connected to GP is the types shown below.
|
-Memory Link SIO type |
|
-Memory Link Ethernet type |
|
-CC-Link type |
|
-OMRON, THERMAC-NEO series |
|
-> Cause 1 |
2. |
If the PLC connected to GP is the type other than those above. |
-> Cause 2 |
|
Cause |
|
Cause 1 |
|
this PLC type does not support Simulation Feature.
Simulation cannot be performed with the selected PLC type. |
|
Cause 2 |
|
When using Simulation Feature, it’s necessary to transfer a program for Simulation to GP in advance. (*1) |
-> Countermeasure |
|
Countermeasure |
|
Go to Project Manager, [Transfer] -> [Setup] -> [Setup] and check [Simulation] and then transfer the screen again. |
|
*1 |
You can check on GP if a program for Simulation is in GP. |
How to check if a program for Simulation is in GP |
Go to Offline of GP. If [SIM-LINK V*.**] doesn’t display at left bottom of the Main Menu screen, the program for Simulation has not been transferred yet. |