产品
下载
联系我们
网站地图
返回首页

微信扫一扫
在线技术支持

微信扫一扫
访问视频号

Otasuke FAQ's Book
 FAQs for getting started
 [No simulation information] displays in Simulation Feature.

When you use Simulation Feature, it’s necessary to transfer a program for Simulation to GP in advance. However if you try Simulation without a program transferred to GP, [no simulation information]'s displayed.

Check the following items.

1. If the PLC connected to GP is the types shown below.

-Memory Link SIO type
  -Memory Link Ethernet type
  -CC-Link type
  -OMRON, THERMAC-NEO series
-> Cause 1
2. If the PLC connected to GP is the type other than those above. -> Cause 2

Cause
  Cause 1
  this PLC type does not support Simulation Feature. Simulation cannot be performed with the selected PLC type.
 
Cause 2
 
When using Simulation Feature, it’s necessary to transfer a program for Simulation to GP in advance. (*1) -> Countermeasure

Countermeasure
  Go to Project Manager, [Transfer] -> [Setup] -> [Setup] and check [Simulation] and then transfer the screen again.

*1 You can check on GP if a program for Simulation is in GP.

How to check if a program for Simulation is in GP
Go to Offline of GP. If [SIM-LINK V*.**] doesn’t display at left bottom of the Main Menu screen, the program for Simulation has not been transferred yet.


Return to Top Close
常见问题 | 个人信息保护 | 关于知识产权 | 使用条款
版权 (C) 2005- Schneider Electric Japan Holdings Ltd.,和普洛菲斯国际贸易(上海)有限公司版权所有,保留所有权利。
沪ICP备05028659号-3