The Enhanced Recipe function is one of three kinds of recipe functions.
You can directly transfer the recipe data (binary type) created on GP-Pro EX from the touch operator interface to the connected device and also can read out the data of the connected device and save them in the touch operator interface. |
|
|
|
There are differences between the Enhanced Recipe function and the other recipe functions as shown below. |
|
Recipe Function
Type |
Enhanced Recipe
|
Filing Data Transfer |
CSV Data Transfer |
Creating data |
GP-Pro EX
Spreadsheet Software
(Excel etc) |
GP-Pro EX |
GP-Pro EX
Spreadsheet Software (Excel etc) |
Data Type |
- Data created on GP-Pro EX (binary type)
- CSV File *1,*2 |
Data created on GP-Pro EX (binary type) |
CSV File |
How to change data |
- Edit on GP-Pro EX
- Edit on Touch Operator
Interface *3 |
- Edit on GP-Pro EX
- Edit on Touch Operator
Interface |
- Edit on GP-Pro EX
- Edit on Touch Operator
Interface |
Data Type to be
handled |
- Word
16 bits/32 bits
Dec/Hex/BCD/Float
- Bit
- Text |
Word
16 bits/32 bits
Dec/Hex/BCD/Float |
Word
16 bits/32 bits
Dec/Hex/Float |
Mixed data type |
|
- |
- |
Address Setup |
Sequential/Random address |
Sequential address only |
Sequential address only |
Using data for
other projects |
*4 |
- |
|
Refine Search/Sort
on Touch Operator
Interface |
*5 |
- |
- |
|
*1: |
A SD card or a USB storage device is required. |
*2: |
The CSV file setting in the SD card/the USB storage device cannot be directly imported to the GP-Pro EX project file. In order to reflect the setup values in the CSV file into the project file, you need to import the CSV file to the internal memory of the touch operator interface once and then receive the project file of the touch operator interface. |
*3: |
Display the keypad on the touch operator interface and edit data, or import data from the SD card/the USB storage device and change data. |
*4: |
Possible by importing the exported CSV file to the touch operator interface’s internal memory. The Enhanced Recipe settings (the number of elements, the data type) should be the same. |
*5: |
Except GP-4*01TW and GP-4401WW |
|
|