 How do I perform Calibration of Analog Units?
How to perform Calibration of Analog Units

4Ch Analog Unit
- Performing Calibration
To set the calibration switch to setting mode, press the CAL SELECT switch until the setting changes from (0, 9 to F) for (disabled) to the desired setting (1 to 8).

The unit can be calibrated for each channel and range, using the calibration perform switch (MIN, MAX), the calibration select switch, and the range switch. To finish calibrating, set the Calibration Select switch to the disabled position (No Operation).

-> Click here for How to set Calibration of Analog Input (FN-AD04AH11).
-> Click here for How to set Calibration of Analog Output (FN-DA04AH11).

2Ch Analog Unit
- Performing Calibration
Both 2Ch Analog Unit of FN-AD02AH41 and FN-DA02AH41 were calibrated when they were assembled. Therefore, it is not possible to be calibrated at the users' end.