 I would like to know specifications of Input/Output of Analog Units

Input/Output of Analog Units

-
4Ch Analog Unit
Analog Input Section iFN-AD04AH11j
Resolution
12 bit
Number of Input Channels
4 ch (Fixed)
Conversion Time
Up to 2 milliseconds
Input Range
0`5V (Impedance 1M Ohm)
1`5V (Impedance 1M Ohm)
0`10V (Impedance 1M Ohm)
-5`5V (Impedance 1M Ohm)
-10`10V (Impedance 1M Ohm)
0`20mA (Impedance 200 Ohms)
4`20mA (Impedance 200 Ohms)
Input Range Switch
Depending on Rotary Switch Settings
Calibration Function
OFFSET / GAIN Setting

Setting the Upper Limit Value / Lower Limit Value

for each range via Switch

Accuracy
0.3%/FS i25Žj
0.5%/FS i0`55Žj
Insulating Method
Photocoupler Insulation

(Input Terminals / between Internal Circuits)

Convert and Process
Simple Average, Running Average

Exclude Max. / Min. Values

Conversion Timing
Convert all Channels at all time ( not selectable)

Analog Output Section iFN-DA04AH11)
Resolution
12bit
Number of Output Channels
4ch (Fixed)
Conversion Time
2msecˆÈ‰º
Output Range
0`5V (Impedance 1M Ohm)
1`5V (Impedance 1M Ohm)
0`10V (Impedance 1M Ohm)
-5`5V (Impedance 1M Ohm)
-10`10V (Impedance 1M Ohm)
0`20mA (Impedance 400 Ohms)
4`20mA (Impedance 400 Ohms)
Output Range Switch
Depending on Rotary Switch Settings
Calibration Function
OFFSET / GAIN Setting

Setting the Upper Limit Value / Lower Limit Value

for each range via Switch

Accuracy
0.3%/FS i25Žj
0.5%/FS i0`55Žj
Insulating Method
Photocoupler Insulation

(Output Terminals / between Internal Circuits)

Conversion Timing
Convert all Channels at all time ( not selectable)

2Ch Analog Unit
¡ Analog Input Section iFN-AD02AH41j
Resolution
12bit
Number of Input Channels
2ch (Fixed)
Conversion Time
Up to 2 Milliseconds
Input Range
0`10V (Impedance 100K Ohms)
0`20mA (Impedance 500 Ohms)
4`20mA (Impedance 500 Ohms)
Current / Voltage

Switch over

Set via Terminal Connection Location
Accuracy
}1%/FS i0`55Žj
Insulating Method
Photocoupler Insulation

(Input Terminals / between Internal Circuits)

Convert and Process
Running Average
Conversion Timing
Convert Channels at all times
Number of Occupied Stations
1 Station

¡ Analog Output Section iFN-DA02AH41)
Resolution
12bit
Number of Output Channels
2ch (Fixed)
Conversion Time
Up to 2 Milliseconds
Output Range
0`10V (Impedance Min. 10K Ohms)
0`20mA (Impedance 10`500 Ohms)
  1. 4`20mA (Impedance 10`500 Ohms)
Current / Voltage

Switch over

Set via Terminal Connection Location
Accuracy
}1%/FS i0`55Žj
Insulating Method
Photocoupler Insulation

(Output Terminals / between Internal Circuits)

Conversion Timing
Convert Channels at all times
Number of Occupied Stations
1Station


Back to page top Return to the previous page