Please check the following points. |
|
|
Is the Bit Address registered in the Alarm Editor ON? |
|
|
|
Have you registered the alarm message on [Bit Log Alarm] or [Word Log Alarm] of [Alarm Editor]? |
|
|
|
|
|
|
|
[Have you set the [State] of [Alarm Editor] ON or OFF?
[If you set [On], alarm occurs when the bit is ON. On the other hand, if you set [Off], alarm occurs when the Bit is OFF. |
|
|
|
|
Is the setting of [Display Start Line]'s value appropriate? (Check from [Q Tag Settings] dialog box→ [.Display Mode]→ [Display Start Line]). At first, set [1] and check the operation. |
|
|
Is the [Size/Color] settings right? Aren't the FG color and the BG color set to be the same? |
|
|
|
|
Is the PLC address registered in [Alarm Editor] right? Please place a lamp on the Base screen and check whether the bit turns ON/OFF. |
|
|
In [Extended Settings] of [GP System Settings], click on [Q Tag Settings] and check if the number of [Q Tag Setting] is not set to zero. |
|
|
|
|
|
|
|
|
|
Execute [Rebuilt] and select [Force System Setup] in [Transfer Settings]. Then, transfer the screen data to GP unit again. |
|
|
|