Error Code |
Description |
Cause or Measures |
00 |
Correctly finished |
GP entered simulation mode while connected to the PLC. |
01 |
Unable to execute in RUN mode |
PLC’s protocol was used to force the GP to RUN mode. |
02 |
Unable to execute in monitor mode |
|
03 |
Unable to execute in P-ROM |
|
04 |
Address Over (limit) |
|
05 |
Unable to execute in program mode |
|
0B |
Unable to execute in debugging mode |
|
0C |
Unable to execute in stand-by mode |
C2000(H) has been set to stand-by mode. |
0D |
Unable toexecute in local mode |
The LK201-V1 mode control switch is set to Local. |
10 |
Parity error |
Noise in data transmission line. |
11 |
Framing error |
Noise in data transmission line. |
12 |
Overrun error |
Reduce the baud rate. |
13 |
FCS error |
Noise in data transmission line. |
14 |
Format error |
|
15 |
Entered/Registered data error |
Designated device does not exist in the PLC. |
16 |
Unused command |
|
18 |
Frame length over max error |
|
19 |
Cannot perform |
The CPU unit is malfunctioning. |
20 |
Cannot create I/O table |
|
21 |
Unable to perform due toPC CPU’s malfunction |
Turn the PC’s power OFF and then ON again. |
22 |
No applicable memory |
|
23 |
Applicable memory is protected. |
|
A0 - A8 |
Data transfer error |
|
B0 |
Unable to execute because the program area is more than 16KB. |
Extension DM is used. |