Feature |
Points |
Remarks |
Details
(Reference Manual) |
Standard I/O |
|
Standard Input *1 |
12 |
--- |
|
Standard Output *1 |
6 |
--- |
|
Special I/O |
|
High Speed Counter (Single-Phase Counter) *1 |
4CH |
Measures single-phase input signals |
|
|
Counter Control |
--- |
Switches up/down. |
|
Preload Input |
--- |
Changes the current value to a value of your choice. |
|
Prestrobe Input |
--- |
Memorizes the current count value. |
|
Synchronize Output |
--- |
Turns on the but when the count value falls within the specified range. |
|
High Speed Counter
(2-Phase Counter) *1 |
2CH |
Measures 2-phase input signals. |
|
|
Counter Control |
|
Switches up/down. |
|
Phase Factor Mode |
--- |
Specify the measuring method. |
|
Preload Input |
--- |
Changes the current value to a value of your choice. |
|
Prestrobe Input |
--- |
Memorizes the current count value. |
|
Synchronize Output |
--- |
Turns on the bit when the count value falls within the specified range. |
|
Marker Input |
--- |
Clears the count value. |
|
PWM Output *1 |
4CH |
Outputs the output frequency pulse using the specified on duty. |
|
Normal Pulse Output *1 |
4CH |
Outputs the set frequency based on the set pulse value. |
|
Acceleration/Deceleration Pulse Output *1 |
4CH |
Increases the pulse to the set frequency for output. |
|
Pulse Catch Input |
4CH |
Imports short pulses (10 microseconds or higher) and turns on the specified bits. |
|