Parts that you can set up with security levels
From among the touch operating parts, you can set each security level for parts with the following features.
Parts |
Feature Details |
---|---|
Switch Lamp |
Bit Switch |
Word Switch |
|
Screen Change |
|
Special Switch (All features) |
|
Selector Switch |
|
Data Display |
Numeric Display (When Allow Input is set) |
Text Display (When Allow Input is set) |
|
Sampling Display |
When Edit Data is set |
Show CSV |
When Edit Data is set |
Action of parts set up with security levels
When a security level is added to a part
You can set interlock with security level if you set a security level for each part.
Current security level < Security level for the part
Interlock is on (the part will not operate).
Current security level >= Security level for the part
Interlock is disabled (the part will operate).
Multiple parts with security levels are placed on top of each other
Only the parts with a security level not higher than the current security level can operate.
Displaying interlocked condition of switches based on security levels
For switch parts, if you select the [Show Interlocked Condition] check box in [Extended] on the [Switch Common] tab, you can set part shapes and labels for the interlocked condition with security levels.
However, this functionality is shared with the interlock feature with [Enable Addresses] enabled. Therefore, you cannot set the shape of the interlock switch separately between addresses and security levels.
When input order is set for the data display
A part with a level higher than the current security level cannot be edited even when it is time to edit the part according to the input order.
When combined with the [Common Settings] menu's [Security] interlock
Security setting for each part can be set together with the interlock setting of [Security] in the [Common Settings] menu.
If both are set, when either of them meets the interlock condition, the operation cannot be performed.
When operating from GP-Viewer EX
As for the operation from GP-Viewer EX, interlock is determined according to the current security level on the GP-Viewer EX side regardless of Synchronous/Asynchronous Mode. It is not dependent on the security level on the server (display unit) side.
For details, refer to the GP-Viewer EX Operation Manual.