23.14.2 Operation Log Contents, Example Output

Example of CSV File Output

Number

Date

Time

User ID

LEVEL

Screen

Parts ID

Comment

Action

Address

IP Adress

1

07/12/22

13:54

 

0

B1

SL_0001

 

Bit Set

[PLC1]M0000

 

2

07/12/22

13:54

 

0

B1

SL_0002

 

Bit Rst

[PLC1]M0001

 

3

07/12/22

1:55 PM

YAMADA

3

B1

SL_0003

Level 3 Switch

Bit Mom

 

192.168.0.1

Item and Description

Items

Description

Number

Log number

Date

Operation data is displayed in the format that is set in [Operation Log Settings].

Time

Operation time is displayed in the format that is set in [Operation Log Settings].

User ID

User ID that is registered in [User ID Mode] (Add User ID) is displayed. For [Level Mode] (Do not add User ID), this will be blank.

LEVEL

Display the level between 0 to 15 at the time of operation.

Screen

Displays the Screen Number as B** for Base Screens, and W** for Window Screens, at the time of operation.

Parts ID

Displays the Parts ID.

Comment

Displays comments in Parts. If nothing is registered, this will be blank.

Action

Displays the action.

23.14.1 Operations To Log

Address

Displays a target address.

IP Address

When using Pro-face Remote HMI to operate the display unit screen, displays the client IP address.

  • To display the IP address, from the [Common Settings] click [Operation Log Settings], then select the [Add IP address to log when operating from Pro-face Remote HMI] check box.
    23.10.2 Operation Log Settings

Sub Info

Address, Action. Sub Info displays when supplemental remarks are needed for the Address or Action.

Prev Value

Displays the previous value.

Chg Value

Displays the changed value. Bit Address displays ON or OFF, Word Address displays a numeric value. The display format of the numeric value differs depends on the display attributes of the parts being used.

Added Info

When recording the operation log, values stored in the specified word addresses will be read. Stores values only when setting up from the [Common Settings] menu's [Operation Log Settings].

23.10.2 Operation Log Settings

  • In the following cases, values are not acquired. Instead they will be shown as "****".

  • When reading word address values failed

  • When invalid addresses or symbols are defined in the Trigger Monitor word address.

  • When trigger bit was not turned ON when trigger monitor is set.

  • When the display format is set to BCD and illegal values are stored, data values stored in word addresses are converted and displayed.

  • When using Indirect Device addresses, instead of the indirect device name, displays the device/PLC name specified by the Device ID. If a Device ID that does not exist is specified, displays questions marks "????".