Features available in GP-Viewer EX are different than those used with the display unit.
Feature |
Details |
Switch |
AUX Output cannot be used.
Special switches related to security, resetting, offline or other unsupported features cannot be used.
If switches overlap, or multiple switch functions are set up, operations may differ from the display unit.
|
Sampling Display |
You cannot edit data.
First gets all sampling information, and then updates at the frequency specified in GP-Viewer EX. From the [Tool] menu click [Settings] and note the [Update Cycle] field.
Refine Search/Sort is available, but it does not synchronize with the display unit.
|
Alarm feature |
The Sub Display feature may be executed at an unexpected time by operation on the display unit even when the Alarm part is not displayed.
Alarm information cannot be cleared by external operation.
Display content may be displayed differently than the display unit (time information, active alarm status, and so on). Touching the [Screen Update] button will update the contents by re-acquiring the alarm information.
You cannot save alarm information.
You cannot perform [Acknowledged] or [Clear] operation.
You cannot perform [Alarm Number Acquisition] operation.
If alarm analysis is used, the analysis list is not shown on the operation log.
Refine Search/Sort is available, but it does not synchronize with the display unit.
|
Logic Programing
Global D-Script
Extended Script |
|
D-script |
|
Trigger Action |
This feature is executed in Asynchronous Mode when the same screen is displayed. In this case, changing screens on the display unit does not change screens in GP-Viewer EX. Therefore, execution of [Start Application] or [Exit WinGP] cannot be confirmed by GP-Viewer EX, so do not perform such operations from GP-Viewer EX.
This feature is enabled in Synchronous Mode. However, the results of drawing are not reflected.
|
Screen Capture |
|
Error |
Displays errors on both the display unit and GP-Viewer EX.
All errors are acquired at first and then the information is updated at the frequency specified in GP-Viewer EX. Click [Change setting] and select [Information of Automatic update frequency].
Errors that are restored will not disappear. Such errors disappear only when the screen is changed.
|
Data Display |
|
Historical Trend Graph |
|
Data Block Display Graph |
|
XY Historical Scatter Graph |
|
XY Block Display Scatter Graph
XY Historical Scatter Graph Normalization |
When quickly changing the control word using D-Script or a PLC with ladder logic on the display unit, server operations may not be detected.
In Asynchronous Mode, when updating the graph, its Display Completion bit does not turn ON. Therefore, the control word cannot be returned to 0 on the display unit. Prior to updating, create a switch that returns the control word to 0.
|
Bulletin Message |
When you perform a display/hide operation continuously, display contents may not be synchronized with the display unit.
In order to update the message, clear the message and display it again.
Display Completion bit cannot be used.
|
Recipes |
|
Enhanced Recipes |
|
File Manager |
|
Internal Devices (LS Area, Memory Link) |
You cannot write data in the Special Relay Area (LS2071 to LS2074, LS2078 to LS2095) from the Viewer.
Write operation into Special Relay Area and Extend System Area is not supported.
|
Security feature |
To change or clear the security level, from the Menu, point to Feature, and select "Change Security Level" or "Change User ID". You can set the security level to 0 if you leave the user ID/password field blank and press the OK button. (This cannot be completed when the security is set for reading Viewer data.)
|
Operation Log |
|
Web Server and FTP Features |
|
RPA Function |
|
Printing feature |
|
Transfer Project File |
|
Monitor |
|
2-color Backlight Switching |
|
Function Key |
|
Playing Movies |
You cannot record or play movies.
Movie Players and Image Unit Displays will not display.
Image Sensor Displays will not show video images.
|
Japanese FEP (Help) |
|
EZ Tower Light |
|
Others |
The status address of each part/function, search status address, and cursor information storage address information cannot be obtained.
Even if [Reverse Display] is enabled in System Settings [Display Unit]-[Display Settings], reverse display is not possible.
The screen does not change to the standby mode. The display unit will switch to standby mode, but the screen will not be changed while the Viewer is connected.
You cannot adjust the brightness and contrast.
Cannot change to offline mode.
A bar code reader cannot be connected.
Cannot be connected to a modem.
You cannot check tag consistency.
Does not respond to the station search of Pro-Server EX.
The time displayed on GP-Viewer EX is based on the time settings of your computer.
|