Since the Generic(AIO) type is fix to word, there are no detailed settings for the unit.
Mode
Select [2CH] or [1CH] in the 2-channel analog unit.
Range
Set the range in the 2-channel analog unit.
0-10V: 0 to 4095
0-20mA: 0 to 4095
4-20mA: 0 to 4095
The range of the 4-channel analog unit is set in the display unit.
0-5V: 0 to 4095
1-5V: 0 to 4095
0-10V: 0 to 4095
-5-5V: -2047 to 2047
-10-10V: -2047 to 2047
0-20mA: 0 to 4095
4-20mA: 0 to 4095
Type
Select the filter type.
2-channel analog
None, Moving Average
4-channel analog
None, Average, Moving Average
For details on filter, refer to Section 2.4 Analog/Digital Conversion, in the "FLEX NETWORK Analog Unit User Manual".
Sampling Frequency
Select the number of samples for A/D conversion. When the filter type is set to [None], this option can be selected.
2-channel analog
2/4/8/16/32/64
4-channel analog
2/4/8/16/32/64/128/256/512/1024/2048/4096/8192/16384/32768/65536
Exclude highest/lowest
Specify whether to remove the maximum and minimum values in the sample data. This option can be selected if the number of samples for A/D conversion is set to 4 or higher.