Example of CSV File Output
| 
 Number  | 
 Date  | 
 Time  | 
 User ID  | 
 LEVEL  | 
 Screen  | 
 Parts ID  | 
 Comment  | 
 Action  | 
 Address  | 
| 
 1  | 
 07/12/22  | 
 13:54  | 
 
  | 
 0  | 
 B1  | 
 SL_0001  | 
 
  | 
 Bit Set  | 
 [PLC1]M0000  | 
| 
 2  | 
 07/12/22  | 
 13:54  | 
 
  | 
 0  | 
 B1  | 
 SL_0002  | 
 
  | 
 Bit Rst  | 
 [PLC1]M0001  | 
| 
 3  | 
 07/12/22  | 
 13:55  | 
 YAMADA  | 
 3  | 
 B1  | 
 SL_0003  | 
 Level 3 Switch  | 
 Bit Mom  | 
| 
 Items  | 
 Description  | 
| 
 Number  | 
 Log number  | 
| 
 Date  | 
 Operation data is displayed in the format that is set in [Operation Log Settings].  | 
| 
 Time  | 
 Operation time is displayed in the format that is set in [Operation Log Settings].  | 
| 
 User ID  | 
 User ID that is registered in "User ID Mode" (Add User ID) is displayed. For "Level Mode" (Do not add User ID), this will be blank.  | 
| 
 LEVEL  | 
 Display the level between 0 to 15 at the time of operation.  | 
| 
 Screen  | 
 Displays the Screen Number as B** for Base Screens, and W** for Window Screens, at the time of operation.  | 
| 
 Parts ID  | 
 Displays the Parts ID.  | 
| 
 Comment  | 
 Displays comments in Parts. If nothing is registered, this will be blank.  | 
| 
 Action  | 
 Displays the action.  | 
| 
 Address  | 
 Displays a target address.  | 
| 
 Sub Info  | 
 This is displayed when supplemental remarks are needed for the Address or Action.  | 
| 
 Prev Value  | 
 Displays the previous value.  | 
| 
 Chg Value  | 
 Displays the changed value. Bit Address displays ON or OFF, Word Address displays a numeric value. The display format of the numeric value differs depends on the display attributes of the parts being used.  | 
| 
 Added Info  | 
 When recording the operation log, values stored in the specified word addresses will be read. Stores values only when setting up from the [Common Settings] menu's [Operation Log Settings]. 
 
 
  | 
![]()
[Number] is addressed sequentially in the file.
The item names are fixed in English.
When starting a display unit or a [CF Card Connection] (or [SD Card Connection]) is selected using the offline Transfer Tool, communication with the device/PLC is not established. The value added to the log is "****".