31.6.2.10 External Driver - Temperature Input Module

Inputs (CH1 to CH4)

Configures settings for module temperature input terminals.

Data Format

Select the thermocouple input data format from [Disable], [K Thermocouple], [J Thermocouple], [T Thermocouple], or [Pt100].

  • When using any data format except [Disable] and while disconnected, an input data error may appear.

K Thermocouple (Celsius/Fahrenheit)

The K thermocouple temperature range is as follows.

The displayed value is 10 times (0 to 13000) the input value ranging from 0.0°C to 1300.0°C.

The displayed value (320 to 23720) is 10 times the input value (32.0°F to 2372.0°F).

J Thermocouple (Celsius/Fahrenheit)

The J thermocouple temperature range is as follows.

The displayed value is 10 times (0 to 12000) the input value ranging from 0.0°C to 1200.0°C.

The displayed value (320 to 21920) is 10 times the input value (32.0°F to 2192.0°F).

T Thermocouple (Celsius/Fahrenheit)

The T thermocouple temperature range is as follows.

The displayed value is 10 times (0 to 4000) the input value ranging from 0.0°C to 400.0°C.

The displayed value (320 to 7520) is 10 times the input value (32.0°F to 752.0°F).

Pt100 Celsius/Fahrenheit

The temperature range of PT100 is shown below.

The displayed value is 10 times (-1000 to 5000) the input value ranging from -100.0°C to 500.0°C.

The displayed value (-1480 to 9320) is 10 times the input value (-148.0°F to 932.0°F).

Output

Configures settings for module analog output terminals.

Data Format

Select a data type from either [Voltage (0-10V)] or [Current (4-20mA)] for analog output.

Fixed

The analog values in the voltage and current output settings appear in the range of 0 to 4095 as shown below.

User Defined (Maximum/Minimum)

The analog values in the voltage and current output settings appear within the range of [Maximum] and [Minimum] settings.

The available values are as follows.

Maximum: minimum to 32767

Minimum: -32768 to maximum

Retain Output

Select whether or not you want to retain output values when the logic is stopped. Select [Enable] to retain output values even if the logic stops.